Fire Sprinkler Testing Follow
In Illinois, fire sprinkler testing is required to ensure that the sprinkler system is functioning properly and in compliance with state and local regulations. The requirements for fire sprinkler testing in Illinois are outlined in the Illinois Administrative Code (Title 41, Part 130, Section 130.100).
Here are the key requirements for fire sprinkler testing in Illinois:
- Frequency of testing: Fire sprinkler systems must be tested at least once a year. There is also a more detailed test required every five years.
- Qualified testing personnel: Testing must be performed by qualified personnel who are knowledgeable and trained in the proper testing procedures and equipment.
- Testing procedures: The testing procedures must include a functional test of the sprinkler heads, control valves, and alarm devices to ensure that they are functioning properly.
- Documentation: The results of the fire sprinkler testing must be documented and maintained on file for at least three years. The documentation must include the date of the test, the name of the person performing the test, and any deficiencies found and corrective actions taken.
- Notification: The testing company must notify the local fire department of the results.
See article “Putting a System on Test” before having the sprinkler system tested.
Comments
0 comments
Please sign in to leave a comment.